Metro tunnels changed the economics of overhead electrification when designers replaced the tensioned catenary with rigid conductor rail: a stiff aluminium rail, usually carrying a copper or stainless contact strip, bolted to insulators at short intervals along the tunnel crown. With no messenger wire, no compensation and almost no sag, the rigid overhead conductor rail suits the tight clearances of a bored tunnel. Yet the electrical architecture of a DC 1500 V metro still needs boundaries between feeding sections, maintenance sections and depot territories — which means a rigid section insulator must exist somewhere in that continuous rail run.
Superficially the task looks identical to the mainline one, and engineers coming from 25 kV AC practice naturally reach for familiar hardware. In practice, rigid-system sectioning devices differ from flexible-system section insulators in almost every dimension that matters: insulation distances, mounting philosophy, alignment tolerances and the electrical behaviour of direct current. Devices built for one duty do not transfer safely to the other.
This article explains how sectioning is engineered in rigid conductor rail systems, why DC 1500 V changes the insulation and arc behaviour, how joint alignment tolerances dominate installation quality, and how single-line and double-line metro devices are selected.
How sectioning works in a rigid conductor rail system
A rigid overhead system is essentially a continuous busbar. Rail lengths are jointed into an electrically and mechanically continuous run, clamped at suspension points spaced a few metres apart along the tunnel. Electrical sectioning therefore cannot rely on cutting a tensioned wire and inserting a floating insulator, as on the mainline; instead, an insulated joint assembly replaces one or more rail lengths, breaking the busbar while presenting an unbroken running surface to the pantograph.
Chinese metro practice formalises this hardware under TB/T 3252-2022, the standard for rigid suspension catenary busbar and components. The FYFH-0.6T-DC rigid section insulator is built to that standard: a DC 1500 V device mounted at rigid suspension points within the conductor rail run, with a design speed of up to 120 km/h, service temperatures from minus 25 to plus 45 degrees Celsius and altitude capability to 2,000 m — environmental limits that reflect metro reality rather than mainline plateau routes. Its construction pairs high-strength insulating elements with aluminium alloy runners and stainless steel fasteners, the latter a deliberate choice against corrosion in humid tunnel air.
Why DC changes the engineering
Two electrical facts dominate. First, the working voltage is far lower than on the mainline — hundreds of volts against twenty-five thousand — so the air gaps and creepage distances can be dramatically shorter. The compact, low-profile geometry that fits inside a tunnel headbox is a direct consequence. Shorter insulation distances in turn shorten the insulating run the pantograph must cross, which eases the mechanical transition.
Second, direct current never crosses zero. An AC arc is extinguished twice per cycle almost as a courtesy of physics; a DC arc keeps burning as long as the circuit and the ionised channel survive. Metro duty then makes matters worse: trains draw heavy current while accelerating, station approaches involve repeated slow passages, and stabling movements cross sectioning points at walking pace. Each such event risks a sustained arc that erodes runners and contact strips aggressively. DC devices answer with arc-resistant runner materials, generous runner lengths relative to the insulation length, and maintenance regimes tuned to passage counts rather than calendar dates.
Joint alignment tolerances
Rigid rail is unforgiving of geometric error. A flexible contact wire absorbs a small height step at a section insulator by deflecting; a rigid rail transmits the step straight into the pantograph head as an impact. Height steps, lateral offsets and gap-width errors at the insulated joints are therefore controlled to tighter tolerances than in flexible installation, and the joint faces are machined rather than field-formed. Runners taper onto the rail surface through shallow ramps, and the assembly must hold its geometry through years of thermal cycling between cold nights and crowded rush-hour tunnels.
Installation practice reflects this discipline. Each insulated joint is set with a measuring frame before torqueing, verified after torqueing, and checked again under a test run of a pantograph-equipped vehicle, because some errors only reveal themselves dynamically. Tunnel possession windows are short and mostly nocturnal, which is one reason metro devices are designed for fast, repeatable mounting at the suspension points rather than for time-consuming in-line wire work.
Rigid-system devices versus flexible-system devices
| Aspect | Rigid conductor rail device | Flexible OCS device |
|---|---|---|
| Mounting | At rigid suspension points | In-line, series in contact wire |
| Tension | None, rail is self-supporting | Carries full wire tension |
| Insulation distances | Short, DC 1500 V levels | Large, 25 kV class levels |
| Arc behaviour | No current zero, arcs persist | 50 Hz zeros truncate arcs |
| Alignment control | Machined joints, tight steps | Wire flex absorbs small error |
Many metros, especially at depots, running tunnels with larger cross-sections and outdoor approaches, operate flexible 1500 V contact line alongside rigid rail, and some device families cover both duties in different sub-models. The distinction then lies less in the insulation than in the mechanical interface: rigid sub-models mount on the rail at suspension points, while flexible sub-models connect in-line and carry wire tension.
Single-line and double-line devices
Selection on a metro is largely a question of track configuration. Twin contact wire arrangements, common where current demand is heavy, need both wires sectioned in a coordinated way; a dedicated double-line device does this in one assembly, preserving the geometric relationship between the wires through the transition. The FYFH-2.0TG-DC double-line section insulator sections both contact wires simultaneously in a single DC 1500 V assembly, rated to 120 km/h with the same minus 25 to plus 45 degree environment, and its design eases installation and alignment inside tunnel possession windows — historically the slowest part of metro sectioning work.

Single-wire tracks, sidings and depot roads are served by single-line devices such as the FYFH-1.0TG-DC single-line section insulator, which offers the same 120 km/h class in a structure sized for constrained metro geometry, with sub-models for rigid or flexible suspension. In the Chuangwit naming convention the numeric prefix again denotes the contact wire tension class of the family and the suffix DC marks the direct-current insulation system, which helps procurement teams keep AC and DC hardware from being mixed on an order.

Specification checklist for tunnel projects
A practical specification for metro sectioning hardware should state the system voltage and short-circuit duty, the suspension type at the installation point, the design speed of the location, and the environmental band — tunnel humidity, condensation and wash-down cleaning are routine in metro service, and fastener materials must survive them. Alignment tolerances and the measuring regime belong in the installation specification, not in a general note. Finally, insist on type test evidence to TB/T 3252-2022 and delivery of the test reports with the goods; on a DC system, arc-resistance testing is the single most predictive document in the file.
For advice on matching single-line, double-line and rigid-mount devices to a specific tunnel geometry, contact our engineering team with the track layout and clearance drawings.